HRN-41
Article no.: EL200153
Single-phase system monitoring: DC and AC, in 3 ranges
-
kostenlose Anfrage / free request
from 1 € 0.00 € 0.00 Incl. 0.00% VAT
The relay is delivered in 2 variants - depending on how the voltage levels are set and monitored.
HRN-41 has a "hysteresis" function, i.e. only the upper level (Umax) is set and the lower level (Umin) is set in % of the upper level. Therefore, the lower level changes automatically as soon as the upper level changes.
HRN-42 has a "window" function, i.e. the upper level (Umax) and the lower level (Umin) are set individually in % of the monitored voltage. Both types have a "MEMORY" function. If the relay enters the fault state, the setting is stored until the reset button is pressed. DIP switch no. 3 is used to set whether the relays should switch independently for each level or in parallel if the voltage level is exceeded or not reached. DIP switch no. 4 is used for hysteresis setting, which takes effect when resetting from fault state to normal state. The relay is protected against reverse polarity of the DC voltage or wrong AC/DC input voltage. This is indicated by simultaneous blinking of both LEDs (LED <U and LED >U).
Operating voltage | AC 110 V, AC 230 V, AC 400 V or AC/DC 24 V (AC 50-60Hz) |
Power consumption | max. 4.5 VA |
Switching output | 250 V AC1 / 24 V DC |
Mechanical life | 3 x 10^7 |
Connection | screw terminals 2.5mm² |
Max. ambient temperature | -20°C to +55°C |
Storage temperature | -30°C to +70°C |
Protection class | IP40 |
Voltage limitation class | III |
Pollution degree | 2 |
Potentiometer | Function |
---|---|
Umax [%U] | Upper limit setting - Umax |
t1 [s] | t1 - delay Umax |
Umin [%Umax] | Lower limit setting - Umin |
t2 [s] | t2 - delay Umin |
DIP | State | Setting |
---|---|---|
DIP-1 | AC | Measured voltage AC |
DC | Measured voltage DC | |
DIP-2 | OFF | Memory function inactive |
ON | Memory function active | |
DIP-3 | 1 | 2nd relay parallel |
2 | 2nd relay independent | |
DIP-4 | 5% | Hysteresis setting 5% |
10% | Hysteresis setting 10% |
Designation | Meaning |
---|---|
Un | Supply display |
>U | Display Umax |
Relay | Output display |
<U | Display Umin |