The DMX512 Demultiplexer DMX-512-3x1-10 is designed for the control of dimmed fluorescent lamps with ECG 1-10V.
There are 3 analog outputs 1-10V available, each of which can be loaded with 40mA. Each analog output has a relay switching output with a load capacity of 230V 1500VA. These relay outputs are designed with a triac pre-ignition for the high inrush currents of the ECGs and are automatically activated depending on the analog values.
The following functions are included:
- Automatic activation of the respective relay output as soon as the DMX value is > "0”
- Relay switch-off delay of 1 second. This avoids unnecessary switching off of the 230V supply during fast control processes.
- OVERSAMPLING error correction (With the so-called "OVERSAMPLING" the module automatically corrects the jumps of the analog values caused by the cycle times of the BUS protocol. In addition, the analog values between the BUS cycles are converted by linearization in the resolution from 8 to 12 bits. This avoids visible steps when dimming fluorescent lamps, for example).
| Type designation | DMX-512D-3x1-10 |
| Article no. | 80101060D |
| Operating voltage | 230V 50/60Hz |
| Output voltage | 3 analog channels, 8 bit resolution (internal 12 bit), 1-10V |
| Sink current (1-10V) | 40mA per channel |
| Relay output | 3 outputs 230V 1500VA (max. 6.5A) with triac zero voltage switch |
| Isolation voltage | 500V (subnet / analog outputs) |
| Connection | pluggable screw terminals |
| Operating temperature | -10°C...+50°C |
| Storage temperature | -25°C...+70°C |
| Protection class | in non-installed state IP30 |
| Design | DIN rail-mounting plastic housing light grey, snap-on on 35mm DIN rail 6 HP |
| Dimensions | WxHxD 106x90x59mm |
| Weight | 280g |
| Brand | ISYnet |
| Compliance | CE |
Function Indicators (LEDs on the Module)
| LED | Designation | State | Meaning |
|---|---|---|---|
| red | Power | Off | No operating voltage |
| On | Operating voltage, no error | ||
| yellow | BUS | Off / On | Error DMX |
| blinking | Interference-free data transmission via DMX line | ||
| green | Regeln | Off | All 3 outputs inactive |
| On | At least one of the outputs > "0” | ||
| green | Notbetr. | Off | Normal operation |
| On | Emergency operation |