The CLS-07T-2P is a convenient solution for lighting controls with standardised 0(1)-10V interface for source and sink operation. The interface can be loaded with 20mA and is used for direct connection of dimmable fluorescent lamps with ECG 1-10V or LV halogen lamps with 1-10V transformer. A hybrid relay switching output with a load capacity of 230V, 1500VA, 6.5A is also available for the analog output. This is optimised for ECG loads by a special zero-crossing circuit and guarantees a safe mains circuit for dimming. By using additional power dimmers, a wide variety of applications and power classes can be realised. The basis of the control unit is a digital, future-oriented multiprocessor technology, which guarantees easy to operate functions and extremely safe operation.
With this control unit, the following functions are available for a dimming circuit:
- I/O
- Bright, dims brighter until the "stop" button is pressed
- Dark, dims darker until the "stop" button is pressed
- Stop, interrupts the dimming process and maintains the current brightness setting
- Preset 1 - calling a fixed dimming position (DIA value)
- Preset 2 - calling a fixed dimming position (DIA value)
- Central on - defined switch on
- Central off - defined switch off
- Signal-on
Up to 7 buttons/contacts (24V) and 3 feedback signals (24V) can be connected to the control unit. 4 potentiometers are available for setting the "switch-on light value" (Einschaltwert), value "Preset 1" and "Preset 2" and the "fade time" (Blendzeit).
Functions can be called up either via a pushbutton panel, single buttons or potential-free contacts.
Control with self-holding function
Variant 1 - I/O
This variant is available for fixed value settings (e.g. exhibition lighting, basic lighting,...).
When switching on (I/O button), the light value set on the potentiometer (switch-on light value) is called up and held. By pressing the I/O button again, the lighting is switched off.
Variant 2 - I/O, Bright, Dark, Stop
Use the "bright", "dark" and "stop" buttons to adjust the brightness individually. The convenience of this type of control lies in the self-retaining function. A single touch on "bright" or "dark" causes the automatic dimming run in the respective direction. If the "stop" button is pressed, the current light value is retained.
Variant 3 - I/O, Bright, Dark, Stop, Preset 1, Preset 2
As described before and additionally 2 presets (fixed values or DIA values) are available. By pressing the corresponding "preset" button the brightness value set at the potentiometer "Preset 1" or "Preset 2" is called up.
Central switching
Higher-level control interventions are possible via the central on (100%) and central off functions. Thus several groups can be switched on or off at the same time (e.g. central control panel at the gatekeeper). A 24V output is available to indicate whether the lighting is still on.
Setting fade time (dimming speed)
With the potentiometer "Blendzeit" the fade time can be adjusted within the range of 0-30 seconds. The dimming time from 0 to 100% is defined as the fade time. A typical default value here is 5 seconds. The dimming with the function buttons always takes place with the set fade time. The output of the analog value when switching on or off takes place without delay.
Electrical Data
Operating voltage | 12V to 35V DC |
Current consumption | 100mA at 24V + current of the feedback signal outputs max. 150mA = sum max. 250mA |
Inputs (buttons) |
24V DC, input current per input 5mA at 24V (only own voltage by bridge can be used!) max. cable length: 50m |
Outputs (feedback signals) |
24V DC 0V switching, against internal + limited to 150mA max. cable length: 50m |
Relay output | 230V 1500VA (max. 6.5A) with triac zero voltage switch |
Analog output | 1 analog channel, 8 bit resolution 0-10V (1-10V), output current max. 20mA (sink or source) |
Connection | screw terminals 2.5mm² pluggable, pluggable spring type terminals 1.5mm² |
Operating temperature | -10°C...+50°C |
Storage temperature | -25°C...+70°C |
Humidity | 0...85% r. h. non-condensing |
Protection class | IP 30 |
Additional Equipment
- Power Supply NT24V/0,75A-S (Article no. 80030007)
- Power Supply NT24V/1,0A-S (Article no. 80030010)
- Power Supply NT24V/2,5A-S (Article no. 80030025)
- Power Supply NT24V/4,0A-S (Article no. 80030040)
- Power Supply NT24V/5,0A-S (Article no. 80030050)