No longer in production - remaining stocks on request!
HCL light control for one room. Simple and uncomplicated.
DALI Interface Light Controller for controlling up to 2x16 (32 in total) DALI ECGs circadian (Tunable white) via a sensor touch panel.
Either the DNR-TC Touch Controller or the DNR-Clock Clock Module can be used to operate the Controller.
Quick Facts
- 2 inputs 230V for buttons
- 1 output 230V for switching off the load
- 2 DALI BUS outputs (max. 16 DALI terminals)
- circadian colour temperature control
- DALI broadcast or addressing
- manual operation
- automatic operation (switching times or astronomical function)
- individual operation according to season possible
The DNR-LC DALI Light Controller is used to control lamps with a colour temperature control based on DALI. The DNR-LC only works in conjunction with the DNR-TC Touch Controller or the DNR-Clock Clock Module.
The functionality is very conveniently managed in an iOS app (see app description). Here you define which functions are assigned to the buttons (on/off, light colour, brightness, manual/auto operation, etc.). The app also provides various switching times, astronomical functions and curve settings.
The module has an integrated DALI power supply and a relay to reduce the standby power of lamps less than 0.5W. It is designed as a lamp installation module with a very small design.
Basic functions:
- (circadian) colour temperature control (Tunable white) / HCL (Human Centric Lighting)
- DALI broadcast or addressing >> group control
- manual operation
- automatic operation according to switching times or astronomical function
- operation during the whole year equal or individual according to 4 seasons
Functions (adjustable with the iOS app):
- setting the DALI operating mode
- circadian curves
- switching times
- functions of the buttons
- functions of motion sensors
- manual/auto definitions
Electrical Data
Operating voltage | 198V-264V AC / 175V-280V DC |
Power consumption | less than 0.5W at 230V AC |
Power switching contact | 230V AC, max. 1000VA |
Button input | 230V, max. 10mA; typical 5mA |
DALI interface | max. 16 DALI ECGs per DALI output, total 32 (with additional equipment expandable up to 128 ECGs with up to 3x DNR-DALI+16) |
Mounting | lamp installation |
Connection | plug-in terminal 0.5-1.5mm² rigid/flexible (8mm stripped) |
Max. ambient temperature | -20°C to +65°C |
Typical Tc point (max.) | +70°C |
Storage temperature | -25°C to +70°C |
Humidity | 1...95% r. h. non-condensing |
Life span |
>50000h at Tc 70°C >100000h at Tc 65°C |
Protection class | IP20 |



4-pole terminal right
9 (DALI2 -) | DALI BUS 2 depending on mode broadcast cold white lamps or addressable |
10 (DALI2 +) | DALI BUS 2 depending on mode broadcast cold white lamps or addressable |
11 (DALI1 -) | DALI BUS 1 depending on mode broadcast warm white lamps or addressable |
12 (DALI1 +) | DALI BUS 1 depending on mode broadcast warm white lamps or addressable |
Additional Equipment
- DNR-TC Touch Controller (Article no. 80100160)
- DNR-Clock Clock Module (Article no. 80100141)
- DNR-LS Light Sensor (Article no. 80100144)
- IR remote control "Lightgate Basic"
- ISYnet adapter RJ10 plugs with 20cm cable (Article no. 80100142)
- If more than 2x16 ECGs are to be connected to a DNR-LC, there is the extension module DNR-DALI+16 (Article no. 80100145). Up to 3 units can be operated with one DNR-LC (max. 4x2x16 = 128 ECGs / 64 lamps possible).
View: